●Conform to GB/T14048.4 and many other national or industry standards. |
●Three-phase electronic type, the trip level is 30. |
●Possess current phase failure and overload protection functions, sensitive phase failure protection, reliable operation, and anti-interference ability Strong, set current value and overload delay are continuously adjustable; and have good inverse time characteristics and other advantages point. |
●The main circuit adopts the core-through current sampling method, combined with advanced electronic (integrated circuit) circuits. |
●Installation method: socket type, Din-rail type installation. |
(1) Company code
(2) Motor protector
(3) Current sampling type (active type)
(4) Design serial number (specification code)
(5) B: Overload alarm (buzzer)
N: With work/test transfer switch
Working power | AC380V、AC220V 50Hz;The allowable voltage fluctuation range is (85%-110%) Ue |
Adjustment method | Online current adjustment by potentiometer |
Output control contact | AS-21:a group of NC contactAS-22:Change over contact 1Z |
Reset mode | Power off reset |
Contact capacity | AC-12,Ue:AC380V, Ie:3A |
Mechanical life | 1×105 time |
Electrical life | 1×104 time |
Installation |
AS-21:Device type/din railtypeAS-22:Device type |
Rated working current |
|||
Model |
Setting current range (A) |
Suitable motor power (kW) |
Minimum sampling current (A) |
AS-21□(JD-5□) |
0.5~5 |
0.25~2.5 |
≥3 |
AS-21□(JD-5□) |
3~30 |
2~15 |
|
AS-21□(JD-5□) |
1~100 |
0.5~50 |
|
AS-21□(JD-5□) |
20~100 |
10~50 |
|
AS-22□(JD-6□) |
63~400 |
30~200 |
10 |
Comparison Table of wire core threading | ||
Motor Power(kW) |
Corresponding setting current(A) |
Core-threading turns (turns) |
0.25~0.5 |
0.5~1 |
12~6 |
0.5~1 |
1~2 |
6~3 |
1~3 |
2~6 |
3~1 |
≥3 |
≥6 |
1 |
Overload Action Time Characteristics | ||||
Trip level |
Different current multiples and action time PT |
|||
1.05Ie |
1.2Ie |
1.5Ie |
7.2Ie |
|
2 |
Tp:no action within 2 hours |
Tp:action within 2 hours |
Tp≤1min |
Tp≤4s |
5 |
Tp≤2min |
0.5s<Tp≤5s |
||
10(A) |
Tp≤4min |
2s<Tp≤10s |
||
15 |
Tp≤6min |
4s<Tp≤15s |
||
20 |
Tp≤8min |
6s<Tp≤20s |
||
25 |
Tp≤10min |
8s<Tp≤25s |
||
30 |
Tp≤12min |
9s<Tp≤30s |
Anti-time characteristic diagram of overload protection
AS-22A
AS-22A/1Z
Diagram (1) The working voltage of the protector is 380V; the AC contactor is 380V
Diagram (2) The working voltage of the protector is 220V; the AC contactor is 220V
AS-22A(1-4.9A、5-49A、20-100A)
AS-22A (40-199A)